EasyManua.ls Logo

ABB ret650 - Page 255

ABB ret650
392 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
The lock-out can then be manually reset after checking the primary fault by
activating the input reset lock-out RSTLKOUT.
If external conditions are required to initiate a closing circuit lock-out but not to
lockout trip, this can be achieved by activating input SETLKOUT. The setting
AutoLock = Off means that the internal trip will not activate lock-out so only
initiation of the input SETLKOUT will result in lock-out. This is normally the case
for overhead line protection where most faults are transient. Unsuccessful
autoreclose and back-up zone tripping can in such cases be connected to initiate
lock-out by activating the input SETLKOUT.
12.1.2.5 Example of directional data
GUID-08AC09AB-2B2F-4095-B06E-1171CF225869 v2
An example how to connect the directional data from different application
functions to the trip function is given below, see Figure
92:
1MRK 504 169-UEN A Section 12
Logic
Transformer protection RET650 2.2 IEC 249
Application manual

Table of Contents

Other manuals for ABB ret650

Related product manuals