GUID-5C22FF3A-320A-47DF-A969-57D3083400FA V1 EN
Figure 89: Detecting incorrect IRF module number
Check that the value of IRF’s parameters does not conflict with the GOOSE
connections in the device.
GUID-B8372066-F5F0-4A81-AE60-5776128D7641 V1 EN
Figure 90: Detecting conflicting with GOOSE connections
Check that both the IRF module number and channel number are either zero or
non- zero.
GUID-8D0C19D4-538B-4FB4-B845-F5DB1BC3423D V1 EN
Figure 91: Detecting IRF module and channel numbers
Check that the physical MAC Address is given in XX-XX-XX-XX-XX format
where X can be [0-9], [a-f] or [A-F].
1MRS757489 A Section 9
Troubleshooting
RIO600 77
Configuration Manual