PROFIdrive parameters
104
963 R Unsigned16 Detected baud rate:
0 = 12 Mbit/s
1 = 6 Mbit/s
2 = 3 Mbit/s
3 = 1.5 Mbit/s
4 = 500 kbit/s
5 = 187.5 kbit/s
6 = 93.75 kbit/s
7 = 45.45 kbit/s
8 = 19.2 kbit/s
9 = 9.6 kbit/s
255 = Invalid baud rate
964 R Unsigned16 Identification number of this device
(0812h)
965 R Octet String2 Profile number of this device (0302h)
Profile 3, Version 2
967 R Unsigned16 Control word (CW)
968 R Unsigned16 Status word (SW)
970 R/W Unsigned16 Load parameter record
Value Description
0 No action
1 Restore factory settings
The parameter must do a zero-to-one
transition and the motor must be stopped.
971 R/W Unsigned16 Save parameter record
Value Description
0 No action
1 Save the drive parameters
to non-volatile memory
The parameter must do a zero-to-one
transition and the motor must be stopped.