Quick start-up guide
25
ABB DRIVES profile (Vendor-specific) with PPO Type 2 (DP-V0)
Drive parameter Setting
ACS800 ACS550
10.01 EXT1 STRT/STP/DIR COMM.CW COMM
10.02 EXT2 STRT/STP/DIR COMM.CW COMM
11.02 EXT1/EXT2 SELECT COMM.CW COMM
11.03 EXT REF1 SELECT COMM. REF COMM
16.01 RUN ENABLE COMM.CW COMM
16.04 FAULT RESET SEL COMM.CW COMM
98.02 COMM. MODULE LINK FIELDBUS
98.02 COMM PROT SEL EXT FBA
98.07 COMM PROFILE ABB DRIVES
51.01 MODULE TYPE PROFIBUS DP*
51.02 NODE ADDRESS 4
51.03 BAUDRATE 1500*
51.04 PPO-TYPE PPO2*
51.05 PZD3 OUT 1202 (CONST SPEED 1)**
51.06 PZD3 IN 104 (CURRENT)**
51.07 PZD4 OUT 2501 (CRIT SPEED SEL)**
51.08 PZD4 IN 105 (TORQUE)**
51.09 PZD5 OUT 2502 (CRIT SPEED 1 LO)**
51.10 PZD5 IN 106 (POWER)**
51.11 PZD6 OUT 2503 (CRIT SPEED 1 HI)**
51.12 PZD6 IN 107 (DC BUS VOLTAGE)**
• • • • • •
51.21 DP MODE 0
51.27 FBA PAR REFRESH REFRESH
*Read-only or automatically detected; **Example