4 PPO-TYPE
This parameter indicates the detected PPO message type for the
PROFIBUS communication. See Figures 6 and 10 in the chapters
DP-V0 communication and DP-V1 communication respectively for
the supported PPO message types.
5 PZD3 OUT
This parameter represents process data word 3 of the PPO type
received by the drive over the PROFIBUS network. The content is
defined by a decimal number in the range of 0 to 32767 as follows:
The parameter area is allocated as follows:
Parameter number with format xxyy, where xx is the parameter
group number (1 to 99) and yy is the parameter number index
inside the group (01 to 99).
0 not used
1 - 99 data set area of the drive
101 - 9999 parameter area of the drive
10000 - 32767 not supported by the drive
The data set area is allocated as follows:
1 data set 1 word 1
2 data set 1 word 2
3 data set 1 word 3
4 data set 2 word 1
5 data set 2 word 2
6 data set 2 word 3
7 data set 3 word 1
...
99 data set 33 word 3