DP-V1 communication
68
The extended Parameter Data bytes are configured via the
PROFIBUS network configuration tool. The functions are defined
in the GSD file.
SAP 62 (Chk_Cfg)
SAP 62 selects the PPO type to be used. The table below gives
the Hex values that must be sent to the drive to select the PPO
type.
*PKW: “Parameter-Kennung-Wert” (Parameter ID Value)
**PZD: “Prozeßdaten” (Process data)
With PPO1, PPO2 and PPO5, reading/writing parameters is only
possible cyclically through the Parameter Identification (PKW)
channel. With PPO3, PPO4 or PPO6, acyclic parameter
reading/writing is available via the DP-V1 parameter read/write
service.
The PPO type can be changed during runtime. However, the
RPBA-01 will go offline while the configuration is being updated.
27 - 28 0-65536 Fail-safe, PZD8
29 - 30 0-65536 Fail-safe, PZD9
31 - 32 0-65536 Fail-safe, PZD10
Cfg_Data (Configuration Data)
Type: Octet String - Length: 4 to 28
PPO
Type
Hex
Values
PROFIdrive parameter enabled
*PKW
size in
bytes
**PZD
size in
bytes
1 F3 F1 Acyclic Parameter Read 8 4
2 F3 F5 Acyclic Parameter Read 8 12
3 F1 Acyclic Parameter Read/Write 0 4
4 F5 Acyclic Parameter Read/Write 0 12
5 F3 F9 Acyclic Parameter Read 8 20
6 F9 Acyclic Parameter Read/Write 0 20