DOC. N° 1SDH000999R0002 - ECN000058721 - Rev. B
SACE Emax 2
Emax E1.2 low voltage air circuit-breakers
Installation, operation and maintenance instructions for
the installer and the user

Table of Contents

Other manuals for ABB SACE Emax 2

Questions and Answers

  • J
    Joseph McdonaldSep 14, 2025
    What does 'Ekip Link Bus' mean on ABB Circuit breakers?
    • K
      kevin03Sep 15, 2025
      This indicates a fault in Ekip Link module. Check for loss of connection with one or more actors (modules) connected to Link Bus.
  • L
    Lisa WalkerSep 14, 2025
    What does 'Ekip Com Hub' mean on ABB SACE Emax 2 Circuit breakers?
    • A
      amytrujilloSep 14, 2025
      This is related to a problem of Ekip Com Hub module with: certificates, connected devices, missing Com modules (RTU or with Ethernet connection), API TLS device, Hub events, parser configuration.
  • A
    April PriceSep 13, 2025
    What does 'Ethernet disconnected' mean on ABB SACE Emax 2 Circuit breakers?
    • V
      Valerie HopkinsSep 13, 2025
      If you see 'Ethernet disconnected' on your ABB Circuit Breakers, it indicates that there is no external cable connected to one or more Ekip Com modules with an Ethernet connection.
  • M
    Maureen KlineSep 12, 2025
    What to do if ABB SACE Emax 2 show 'Battery low'?
    • G
      gboydSep 12, 2025
      If the ABB Circuit Breakers display a 'Battery low' message, you should change the battery. Consult the 1SDH001000R0509 kit sheet for instructions.
  • M
    monicawallaceSep 12, 2025
    How to fix invalid date on ABB SACE Emax 2?
    • J
      jamiealvarezSep 12, 2025
      If you receive an 'Invalid Date' error on your ABB Circuit Breakers, it means the date and time are incorrect. You can correct this by going to Settings-System-Date and Settings-System-Time to set the correct date and time.
  • R
    Robin BarrySep 10, 2025
    Why does my ABB SACE Emax 2 show a 'Local bus' error?
    • S
      Scott GreenSep 10, 2025
      If you have 'Local Bus' alarm on your ABB Circuit Breakers, it could be due to several reasons. The unit might be on with auxiliary supply, the Local Bus parameter could be enabled without a connection to the modules, or the connection is incorrect, or communication has been lost for more than five seconds. To resolve this, check the connection and powering of modules in the terminal box or externally, and ensure that the connected modules are compatible with Ekip Touch.
  • Y
    yatesshawnSep 8, 2025
    How to troubleshoot ABB SACE Emax 2 when it is not possible to perform the trip test?
    • R
      Robert SandersSep 8, 2025
      If it is not possible to perform the trip test: * Trip coil is not connected properly. Check Trip coil connection and messages on display. * CB trip signal has not been reset. Press the reset pushbutton. * The busbar current is greater than zero. Correct operating condition.
  • M
    Michael AguilarAug 25, 2025
    Why ABB SACE Emax 2 Circuit breakers fails to react to opening/closing command from Ekip Touch?
    • M
      Misty HughesAug 26, 2025
      The ABB Circuit breaker might fail to react to opening/closing command from Ekip Touch because: * The connections or supplies of the opening/closing actuators are not correct. Check connections and supplies. * There is an absence of auxiliary power supply to Ekip Touch. Check supplies and status of Power LEDs. * The Circuit-breaker is in a condition which fails to enable the selected command. Check circuit-breaker documentation and cases that fail to enable command.
  • K
    Krista LopezAug 27, 2025
    How to fix communication problems with Ekip Com, Ekip Link, Ekip Signalling or Ekip CI in ABB SACE Emax 2?
    • D
      diazryanAug 27, 2025
      If you're experiencing communication problems with Ekip Com, Ekip Link, Ekip Signalling, or Ekip CI in your ABB Circuit breakers, it might be due to the circuit-breaker being in the withdrawn position, Vaux being absent, or modules not inserted properly. To resolve this, insert the modules, set the circuit-breaker to the Connected position, and connect Vaux.
  • B
    Benjamin EdwardsAug 28, 2025
    What causes ABB Circuit breakers not to open when the opening coil is powered?
    • J
      Jonathan KimAug 28, 2025
      The ABB circuit-breaker may not open when the opening coil is powered due to: * The operating mechanism being blocked. Contact ABB. * The power supply voltage of the auxiliary circuits being too low. Measure the voltage: it should not be lower than 85 % of the rated voltage of the coil. * The power supply voltage being different from that indicated on the rating plate. Use the correct voltage. * The cables of the coil not being inserted correctly in the terminals. Make sure there is continuity between cable and terminal and if necessary reconnect the cables of the coil to the terminals. * The connections of the power supply circuit being wrong. Check the connections using the relevant wiring diagram. * The opening coil being damaged. Replace the coil.

Summary

Transport and Checking on Receipt

Description

Circuit-breaker Overview

Details of circuit-breaker types, structure, and components.

Environmental Conditions

Installation Environment

Requirements for dry, dust-free installation locations, and environmental factors.

Installation

Warnings and Precautions

Safety guidelines before starting installation procedures.

Ekip Protection Trip Units

Introduction and Trip Unit Overview

General introduction to Ekip trip units, types, and functions.

Ekip Dip Interface and Protections

Details of the Ekip Dip interface, operator controls, and protection functions.

Accessories

Putting into Service and Maintenance

Putting into Service

General checks and procedures for initial setup and commissioning.

Alarms and Failures

Identifying and resolving faults, causes, and error signals.

Maintenance Operations

Procedures for inspection, cleaning, lubrication, and testing.

ABB SACE Emax 2 Specifications

General IconGeneral
TypeAir circuit breaker
Rated Current800 A to 6300 A
Breaking CapacityUp to 150 kA at 415 V AC
Frequency50/60 Hz
Number of Poles3, 4
InstallationFixed or withdrawable
StandardsIEC 60947-2
Trip UnitEkip Touch, Ekip Hi-Touch
CommunicationModbus, Profibus, Ethernet
Rated Voltage690 V AC