Why is it not possible to charge the closing springs by means of the gearmotor in ABB SACE Emax 2 Circuit breakers?
- FFranklin PerrySep 3, 2025
If it is not possible to charge the closing springs by means of the gearmotor, it could be due to: * The cables of the gearmotor are not inserted correctly in the terminals. Make sure there is continuity between cable and terminal and if necessary reconnect the cables of the gearmotor to the terminals. * The connections of the power supply circuit are wrong. Check the connections using the relevant wiring diagram. * The circuit-breaker is in disconnected position. Switch the circuit-breaker to the test or connected position. * The gearmotor protection internal fuse has tripped. Replace the fuse. * The gearmotor is damaged. Replace the gearmotor.