EasyManua.ls Logo

ABB SACE PR021/K - 4. Special Functions; 4.1. Reset; 4.2. Reset Signals; 4.3. Self-Test Function

ABB SACE PR021/K
52 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
L3016
1SDH000559R0002
10/52
ABB SACE
SACE PR021/K
4. Special functions
4.1. Reset
The PR021/K unit can be reset by pressing the ‘Reset’ push-button on the front panel of the unit (see par. 3.1).
This type of reset restarts the Sw of the PR021/K unit (the data stored in the RAM are erased).
4.2. Reset signals
“Reset signals” causes the internal relays (K51/1...8) to be returned to their rest condition (contact open).
If the “AUTOMATIC RESET” function is not selected, to reset the signals, proceed as follows:
- carry out a reset (see par. 4.1), if the applicable scenario is “PR021/K in Master mode” (see par. 1.2)
- send a “Trip Reset “ command from the remote supervision system
- carry out a reset (see par. 4.1), if the applicable scenario is “PR021/K in Slave mode” (see par. 1.2), on the Emax series
protection unit (PR112 or PR113).
If the “AUTOMATIC RESET” function is selected, to reset the signals simply carry out a trip reset on the protection unit
and the signals on the PR021/K unit will also be reset automatically.
4.3. Self-test function
To carry out the self-test, dip-switch no. 1 must be set to ON (see par. 5.3) then the reset push-button is pressed.
The self-test switches all 8 internal relays of the unit in sequence, and activates the related indicator LED
K51/1...K51/8 (see par. 3.2).
The Tx/Rx LED lights on each switching, and once the self-test is finished, it will flash according to the indications listed
in par. 3.2.
The self-test takes approx. 10s, thereafter the SACE PR021/K unit automatically returns to normal operation.
N.B. If dip-switch no. 1 is ON, the Self-test function is also activated when the PR021/K unit is powered on.
4.4. Stand-by function
To select the Stand-by mode, dip-switch no. 8 must be set to ON (see par. 5.3) then the reset push-button is pressed;
in this operating mode, the internal relays of the unit will not be switched (but the related indicator LEDs K51/1...K51/8
will still light).
While operating in Stand-by mode, the Tx/Rx LED will flash according to the instructions listed in par. 3.2.
This function is used when the protection unit is being tested (for example with PR010/T unit) and switching of the relays
of the PR021/K unit is not desired.
N.B. If dip-switch no. 8 is ON, the Stand-by function is also activated when the PR021/K unit is powered on.

Related product manuals