ABB | SACE Tmax XT
External electronic accessories | 10 - Ekip Com Hub167 | © 2020 ABB | 1SDH001821A1002 - ECN000135670
Interface
the module has three signaling leds:
1
2
Figure 51
LEDs Description
Power
Signals the on status and correct communication with Ekip Touch:
• off: module off
• on steady or flashing synchronized with the Power led of Ekip Touch: module on
and communication with Trip unit present.
• flashing not synchronized with the Power led of Ekip Touch (2 fast flashes per
second): module on and communication with Trip unit absent.
Link (1)
Indicates the communication state:
• off: incorrect connection, signal absent.
• on steady: connection correct
Activity (2)
Indicates the communication state:
• off: no activity on line
• flashing: activity on line present (receiving and/or transmitting)
Configurations via menu
Local bus activation, which is essential for starting the communication between module and Ekip Touch, is
available in the Settings menu (page 37).
The following communication parameters can be configured if the module has been correctly detected by
Ekip Touch in the Settings-Modules menu:
Parameter Description Default
Enable Switches communication between module and server on/off.
Static IP address ON
Defines whether the module has the dynamic (Off) or static (On)
IP address.
If = On all the associated parameters are enabled
Off
Static address IP address Enables the static IP to be selected 0.0.0.0
Static Network Mask Enables the subnet mask to be selected 0.0.0.0
Static Gateway address
When there are several subnets, enables the IP address of the
node to which the module is connected to be selected
0.0.0.0
Enable SNTP client
Allows the SNTP protocol for distribution of the clock and
synchronization signal to be enabled.
Off
SNTP Server Addr. Allows the network server that supplies the SNTP to be set. 0.0.0.0
Password code required to register module on Cloud ---
Remote firmware update
Enables the firmware of the module to be updated. There are two
parameters:
• Enable, to configure firmware download
• Automatic, to automate module updating
Off
Automatic