ABB | SACE Tmax XT
38 | © 2020 ABB | 1SDH001821A1002 - ECN000135670 Ekip Touch - Interface and menus | 4 - Menu
Installation menu
If Ekip Touch detects that Rating Plug or Ekip Measuring have not been installed properly, it signals an alarm
(page 19) and completes Settings menu with the specific installation section:
Menu Submenus 1 Submenus 2 Commands
Circuit Breaker Installation
Rating Plug Install
Ekip Measuring Install
Correct installation is confirmed by a message on the display and disappearance of the alarm signal and
installation menu.
NOTE: availability of submenus depends on the module, which appears to have not been
installed
Test Menu
Menu Submenus
Description, parameters and Comman-
ds
Page
Autotest - Autotest command 133
Trip Test - TRIP command 133
Test CB - Close CB, Open CB 133
Ekip CI - Autotest command 134
Ekip Signalling 2K
(1)
Ekip Signalling 2K-1
(1)
Module autotest command 134Ekip Signalling 2K-2
(1)
Ekip Signalling 2K-3
(1)
ZoneSelectivity
(2)
S Protection
(3)
Input, Force Output, Release Output 134
G Protection
(4)
Rc Test
(5)
- Test instructions 134
(1)
available if one or more Ekip Signalling modules are connected and detected by Ekip Touch
(2)
available if Ekip Touch is on with auxiliary supply
(3)
available with S and/or S2 and/or D protection enabled, for S protection the set curve must be t=k
(4)
available with G and/or Gext and/or MDGF and/or D protection enabled and curve t=k
(5)
available with Rating Plug and Rc toroid present
(6)
available if the Ekip CI module is connected and detected by Ekip Touch
About Menu
Menu Submenus Information provided
Protection Unit -
Information about Ekip Touch: Mainboard serial
number, Trip unit serial number, type, version,
standard, SW version, date and time, language
Circuit Breaker -
CB information: TAG name, CB name, rated current,
number of poles, CB status and position, total
operations, CB serial number
IEC61557-12
(1)
-
Status of 1% measurements (from Class 1 Power
& Energy Metering package), serial number of
assembly and current sensors connected
Feature Collection - List of tripped protections in Trip unit
Modules Modul x
(2)
Module information: serial number, SW version,
status of inputs/outputs/contacts (if present)
(1)
available if Class 1 Power & Energy Metering SW package is provided for by Trip unit module or if it has been
previously activated
(2)
available if one or more modules are connected and detected by unit