24
Serial communica-
tion parameters
Apart from the event codes the substation level
data communicator is able to read, over the
SPA-bus, all input data (I-data) of the module,
setting values (S-data), information recorded in
the memory (V-data), and some other data.
Further, part of the data can be altered by
commands given over the SPA-bus.
Data Channel Code Data Values
direction
Current in phase L1 (x I
n
) 0 I1 R 0.00…2.50 x I
n
Current in phase L2 (x I
n
) 0 I2 R 0.00…2.50 x I
n
Current in phase L3 (x I
n
) 0 I3 R 0.00…2.50 x I
n
Active power (bits) 0 I4 R -1023…1023 bits
Reactive power (bits) 0 I5 R -1023…1023 bits
Current in phase L1 (A) 0 I6 R 0…9999 A
Current in phase L2 (A) 0 I7 R 0…9999 A
Current in phase L3 (A) 0 I8 R 0…9999 A
Status of an object 1…3 I1 R 0 = undefined (inputs 00)
1 = closed
2 = open
3 = undefined (inputs 11)
Closed status of an object 1…3 I2 R 0 = not closed
1 = closed
Open status of an object 1…3 I3 R 0 = not open
1 = open
Status of inputs 4…13 4…13 I1 R 0 = not active
1 = active
Direct output write 1…3 O1 W 0 = open
1 = close
Open select 1…3 V1 RW 0 = non select
(secured operation) 1 = select
Close select 1…3 V2 RW 0 = non select
(secured operation) 1 = select
Execute selected open/close 1…3 V3 W 1 = execute selected
operation operation
Cancel selected open/close 1…3 V4 W 1 = cancel selected
operation operation
Open pulse length 1…3 V5 RW(e) 0.1…100.0 s
Close pulse length 1…3 V6 RW(e) 0.1…100.0 s
Execute selected open/close 0 V251 W 1 = execute all selected
operation (common addr. 900) operations
Cancel selected open/close 0 V252 W 1 = cancel all selected
operations (common addr. 900) operations
kWh value per pulse 0 S3 RW(e) 0.01…1000 kWh
per pulse
Position of switch SG1/1 0 S6 R 0 = operation position
(SG1/1=0)
1 = interlockings off
(SG1/1=1)
Object indication mode 0 S7 RW(e) 0 = continuous display
1 = automatic switch-off
after 10 min.
Display indication mode 0 S8 RW(e) 0 = continuous display
1 = automatic switch-off
after 5 min.