25
Data Channel Code Data Values
direction
Scaling of current measurement 0 S9 RW(e) 0.00…10000.00
Low limit for mA signal of active power 0 S12 RW(e) -20…+20 mA
High limit for mA signal of active power 0 S13 RW(e) -20…+20 mA
Low limit for mA signal of react. power 0 S14 RW(e) -20…+20 mA
High limit for mA signal of react. power 0 S15 RW(e) -20…+20 mA
Active power corresponding to the
mA signal at low limit 0 S16 RW(e) - 999.99…+999.99
Active power corresponding to the
mA signal at high limit 0 S17 RW(e) - 999.99…+999.99
Reactive power corresponding to the
mA signal at low limit 0 S18 RW(e) - 999.99…+999.99
Reactive power corresponding to the
mA signal at high limit 0 S19 RW(e) - 999.99…+999.99
Power measurement 0 S91 RW(e) 0 = no power
measurement
1 = power is measured
Energy measurement 0 S92 RW(e) 0 = no energy
measurement
1 = energy is measured
Configuration and interlocking 0 S100 RW(e) 0 = freely programmable
configuration and
interlocking program
1 = default 1
2 = default 2
10 = default 10
Configuration of objects 0 S101 RW(e) - value 1;
(format; value 1, value 2, input No, : 0 = indicator not used
output No, value 3) S116 1 = indicator used
- value 2;
0 = vertical LEDs indicate
open status
1 = vertical LEDs indicate
closed status
- input number;
1…3 = input number 1…3
- output number;
0 = not controlled object
20 or 21 = outputs 20 and
21 used
- value 3;
0 =object other than a CB
1 = object is a CB
Program/run mode selection 0 S198 RW(e) 0 = program mode
1 = run mode
Interlocking selection 0 S199 RW(e) 0 = no interlockings
1 = interlockings in use
2 = for future use