26
Data Channel Code Data Values
direction
Interlocking and Conditional Direct 0 M200 RW(e) operation =
Output Control program : LOAD, LOADN
(format; operation, operand) M300 AND, ANDN
OR, ORN
OUT
END
operands for interlocking =
status closed (1…3)
or active (4…13)
status undefined
(101…103)
status open
(201…203)
No. of output
(20 or 21)
No. of memory
(70…89)
operands for Conditional
Direct Output Control =
status closed (1…3)
or active (4…13)
status undefined
(101…103)
status open
(201…203)
No of output
(22…24, 220 or 221)
No of memory
(70…89)
Event delay; —>10 (open) 1…3 S10 RW(e) 0.0, or 0.1…60.0 s
Event delay; —>01 (close) 1…3 S11 RW(e) 0.0, or 0.1…60.0 s
Event delay; —>11 (undefined) 1…3 S12 RW(e) 0.0, or 0.1…60.0 s
Event delay; —>00 (undefined) 1…3 S13 RW(e) 0.0, or 0.1…60.0 s
Use of input 7 7 S1 RW(e) 0 = general mode
1 = pulse counter without
indication
2 = pulse counter with
indication
Operation direction of 4…13 S2 RW(e) 0 = active at low state
inputs 4…13 1 = active at high state
Signal output activation by 4…13 S3 RW(e) 0 = no SIGNAL output
inputs 4…13 22 = SIGNAL1 output is
activated
23 = SIGNAL2 output is
activated
24 = SIGNAL3 output is
activated
Operation of OPEN and CLOSE 4…13 S4 RW(e) 0 = no activation or inhibit
outputs by inputs 4…13 20 = activate OPEN
output
21 = activate CLOSE
output
120 = inhibit OPEN
output
121 = inhibit CLOSE
output