27
Data Channel Code Data Values
direction
Memory controlled function of the 4…9 S5 RW(e) 0 = not memory
indicators of the binary inputs controlled
1 = memory controlled
Event delay; —>activated 4…13 S10 RW(e) 0.0, or 0.1…60.0 s
Event delay; —>reset 4…13 S11 RW(e) 0.0, or 0.1…60.0 s
Event reporting 1…13 S20 RW(e) 0 = event reporting
enabled
1 = event reporting
inhibited
Active power (MW) 0 V3 R -999.99…+999.99 MW
Reactive power (Mvar) 0 V4 R -999.99…+999.99 Mvar
Active energy (kWh) 0 V5 RW 0…999999999 kWh
Status of the local/remote key switch 0 V6 R 0 = local
1 = remote
Active energy (kWh) 0 V8 RW 0…999 kWh
Active energy (MWh) 0 V9 RW 0…999 MWh
Active energy (GWh) 0 V10 RW 0…999 GWh
Active energy; reversed (kWh) 0 V11 RW 0…999 kWh
Active energy; reversed (MWh) 0 V12 RW 0…999 MWh
Active energy; reversed (GWh) 0 V13 RW 0…999 GWh
Reactive energy (kvarh) 0 V14 RW 0…999 kvarh
Reactive energy (Mvarh) 0 V15 RW 0…999 Mvarh
Reactive energy (Gvarh) 0 V16 RW 0…999 Gvarh
Reactive energy; reversed (kvarh) 0 V17 RW 0…999 kvarh
Reactive energy; reversed (Mvarh) 0 V18 RW 0…999 Mvarh
Reactive energy; reversed (Gvarh) 0 V19 RW 0…999 Gvarh
Data store into EEPROM 0 V151 W 1 = store, takes about 5 s
Load default values after EEPROM 0 V152 RW(e) 0 = enable to load default
failure values
1 = inhibit to load default
values
Event mask 0 V155 RW(e) 0…15
Event mask 1…3 V155 RW(e) 0…2047
Event mask 4…13 V155 RW(e) 0…15
Activation of self-supervision output 0 V165 W 0 = reset
1 = activate
Internal fault code 0 V169 R Fault code
Data communication address 0 V200 RW(e) 1…255
Data transfer rate 0 V201 RW(e) 4800, 9600
Program version symbol 0 V205 R E.g. 054 A