17
—
Test diagrams for systems with integral
ground fault protection
—
Fig. 6 Main circuit breaker with integral ground fault protection - 3-Phase, 4-wire
Test
no.
Connect
Test Current
Supply to
Points
Connect
Jumper
between
points
Results expected Comments
Circuit breaker
should not trip
This confirms that polarity and ampere
rating of the neutral sensor match those of
the phase sensors in the circuit breaker
Circuit breaker
should trip at ground
fault setting.
Confirms continuity of round path from
ground bus to neutral
* In 3-wire equipment the load neutral is not furnished. Omit Test 10-1.
Transformer wiring diagram shown as reference only.
This figure is indicated for Internal ground fault protection EKip TU with ABB provided
external ground fault neutral sensor.
NOTE: High Current supply capable of delivering up to .2x ATS amperage, jumper
cables.
—
Table 3
N
3-phase, 4- wire
Transformer
N1
A1
Breaker
G1
A2
N2
ATS
Ground
Fault
Test
Current
Supply
To Loads
Ground Bus
N*
NCT