EasyManua.ls Logo

ABB Tmax XT - Page 25

ABB Tmax XT
26 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
45
46
XT5 TM
SACE Tmax XT| ABB
2
MAX
MED
MIN
l3
MAX MED MIN MAX MED MIN
l1(40°C)
MAX
MED
MIN
TMA
N
N
ln =
1
TMA
In
300
400
500
600
MIN (5xIn)
1500
2000
2500
3000
MED (7,5xIn)
2250
3000
3750
4500
MAX (10xIn)
3000
4000
5000
6000
I3
TMG
In
300
400
500
600
MIN (2,5xIn)
750
1000
1250
1500
MED (3,75xIn)
1125
1500
1875
2250
MAX (5xIn)
1500
2000
2500
3000
I3
MA
In
300
400
500
MIN (7xIn)
2100
2800
3500
MED (10xIn)
3000
4000
5000
MAX (13xIn)
3900
5200
6500
I3
TMA
TMG
In
300
400
500
600
MIN (0,7)
210
280
350
420
MED (0,85)
255
340
425
510
MAX (1xIn)
300
400
500
600
I1
300
400
500
600
210
280
350
420
255
340
425
510
300
400
500
600
Trip unit
In
Volt
rating
Threshold current
Intermediate point
Interrupting rating
Vac
Irms
Ip
2
I t
Irms
Ip
2
I t
Irms
Ip
2
I t
kA
kA
6 2
10 A s
kA
kA
6 2
10 A s
kA
kA
6 2
10 A s
XT5H
TMG,
TMA,
Ekip
Up to
600A
(a)(b)
480Vac
25
31,4
2,8
42
40
3,6
65
47,9
4,2
XT5L
TMG,
TMA,
Ekip
Up to
600A
(a)(b)
480Vac
35
37,1
2,9
65
47,9
4,2
100
51,4
4,2
XT5V
TMG,
TMA,
Ekip
Up to
600A
(a)(b)
480Vac
25
33,4
2,8
100
62,2
4,9
150
62,2
4,9
(a) Includes TMF, TMA with In = 300 - 400 - 500 - 600 A
(b) Includes Ekip with In = 250 - 300 - 400 - 600 A
Current limiting performances

Related product manuals