Page #137 background image
TPU2000/2000R Modbus/Modbus Plus Automation Guide
127
Register
Address
Item Description (Multiplier if any)
02 = Alternate 1 Settings
03 = Alternate 2 Settings
41925 Fault Record Number
Unsigned 16 Bit
(1 – 999, only last 32 kept)
41926 Year 2 digit 00 -99 Unsigned 16 Bit Year of Fault
41927 Month 1 - 12 Unsigned 16 Bit Month of Fault
41928 Day 1 - 31 Unsigned 16 Bit Day of Fault
41929 Hour 00 - 23 Unsigned 16 Bit Hour of Fault
41930 Minute 00 - 59 Unsigned 16 Bit Minute of Fault
41931 Second 00 - 59 Unsigned 16 Bit Second of Fault
41932 Hundredths of Seconds 0 - 99 Unsigned 16 Bit Hundredth Second of Fault Time
41933 Winding1 Tap Unsigned 16 Bit (X 10)
41934 Winding2 Tap Unsigned 16 Bit (X 10)
41935 I operate Phase A Unsigned 16 Bit (X 800)
41936 I operate Phase B Unsigned 16 Bit (X 800)
41937 I operate Phase C Unsigned 16 Bit (X 800)
41938 I restraint Phase A-Winding 1 Unsigned 16 Bit (X 800)
41939 I restraint Phase B-Winding 1 Unsigned 16 Bit (X 800)
41940 I restraint Phase C-Winding 1 Unsigned 16 Bit (X 800)
41941 I restraint Phase A-Winding 2 Unsigned 16 Bit (X 800)
41942 I restraint Phase B-Winding 2 Unsigned 16 Bit (X 800)
41943 I restraint Phase C-Winding 2 Unsigned 16 Bit (X 800)
41944 2nd Harmonic Phase A-Winding 1 Unsigned 16 Bit (X 2)
41945 5th Harmonic Phase A-Winding 1 Unsigned 16 Bit (X 2)
41946 All Harmonic Phase A-Winding 1 Unsigned 16 Bit (X 2)
41947 2nd Harmonic Phase B-Winding 1 Unsigned 16 Bit (X 2)
41948 5th Harmonic Phase B-Winding 1 Unsigned 16 Bit (X 2)
41949 All Harmonic Phase B-Winding 1 Unsigned 16 Bit (X 2)
41950 2nd Harmonic Phase C-Winding 1 Unsigned 16 Bit (X 2)
41951 5th Harmonic Phase C-Winding 1 Unsigned 16 Bit (X 2)
41952 All Harmonic Phase C-Winding 1 Unsigned 16 Bit (X 2)
41953 2nd Harmonic Phase A-Winding 2 Unsigned 16 Bit (X 2)
41954 5th Harmonic Phase A-Winding 2 Unsigned 16 Bit (X 2)
41955 All Harmonic Phase A-Winding 2 Unsigned 16 Bit (X 2)
41956 2nd Harmonic Phase B-Winding 2 Unsigned 16 Bit (X 2)
41957 5th Harmonic Phase B-Winding 2 Unsigned 16 Bit (X 2)
41958 All Harmonic Phase B-Winding 2 Unsigned 16 Bit (X 2)
41959 2nd Harmonic Phase C-Winding 2 Unsigned 16 Bit (X 2)
41960 5th Harmonic Phase C-Winding 2 Unsigned 16 Bit (X 2)
41961 All Harmonic Phase C-Winding 2 Unsigned 16 Bit (X 2)
41962 I restraint Phase A-Winding 1 (Ang) Unsigned 16 Bit
41963 I restraint Phase B-Winding 1 (Ang) Unsigned 16 Bit
41964 I restraint Phase C-Winding 1 (Ang) Unsigned 16 Bit
41965 I restraint Phase A-Winding 2 (Ang) Unsigned 16 Bit
41966 I restraint Phase B-Winding 2 (Ang) Unsigned 16 Bit
41967 I restraint Phase C-Winding 2 (Ang) Unsigned 16 Bit
41968 Winding 1 Tap Unsigned 16 Bit (X 10)
41969 Winding 2 Tap Unsigned 16 Bit (X 10)
41970 I Operate Phase A Unsigned 16 Bit (X 800)
41971 I Operate Phase B Unsigned 16 Bit (X 800)
41972 I Operate Phase C Unsigned 16 Bit (X 800)
41973 I Restraint Phase A-Winding 1 Unsigned 16 Bit (X 800)
41974 I Restraint Phase B-Winding 1 Unsigned 16 Bit (X 800)
41975 I Restraint Phase C-Winding 1 Unsigned 16 Bit (X 800)