TPU2000/2000R Modbus/Modbus Plus Automation Guide 
323 
    0  not used reserved for fixed DIFF TRIP 
    1  Contact OUT5 
    2  Contact OUT7 
    3  Contact OUT4 
    4  Contact OUT6 
    5  Contact OUT3 
    6  Contact OUT2 
    7  Contact OUT1 
    8  spare 
    9  spare 
    10  spare 
    11  spare 
    12  spare 
    13  spare 
    14  spare 
    15  spare 
 
11.7 Receive Programmable Output User Defined Names (3 11 7)
 
 
User definable 8 char output strings. Byte 9 is an implied NULL. 
Msg byte
 Definition 
1/1    Most significant high byte of password 
1/2    Most significant low byte of password 
1/3    Least significant high byte of password 
2/1    Least significant low byte of password 
2/2   spare 
2/3    Command + Subcommand = 0xb7 
3/1-5/2    OUT1 Character String 8 bytes 
5/3-8/1    OUT2 Character String 8 bytes 
8/2-10/3   OUT3 Character String 8 bytes 
11/1-13/2  OUT4 Character String 8 bytes 
13/3-16/1  OUT5 Character String 8 bytes 
16/2-18/3  OUT6 Character String 8 bytes 
19/1-21/2  OUT7 Character String 8 bytes 
21/3-24/1  spare Character String 8 bytes 
24/2-26/3  spare Character String 8 bytes 
27/1-29/2  spare Character String 8 bytes 
29/3-32/1  spare Character String 8 bytes 
32/2-34/3  spare Character String 8 bytes 
35/1-37/2  spare Character String 8 bytes 
37/3-40/1  spare Character String 8 bytes 
40/2   Checksum high byte 
40/3    Checksum low byte 
 
11.8,9,10 Receive Relay Settings  ( 3 11 X )
 
 
( 3 11 8 ) = Primary Settings 
( 3 11 9 ) = Alternate 1 Settings 
( 3 11 10 ) = Alternate 2 Settings 
 
Low byte consists of bits 0 through 7. 
High byte consists of bits 8 through 15. 
 
Curve Selection Type I
 
0 = Extremely Inverse 
1 = Very Inverse 
2 = Inverse 
3 = Short Time Inverse 
4 = Definite Time