TZIDC, TZIDC-200 DIGITAL POSITIONER | COI/TZIDC/TZIDC-200-EN REV. B 41
Error code
Possible cause
Impact
Troubleshooting the Instrument
Error while processing the measured
values, pointing to an error in the working
data (RAM).
The actuator is moved to
the safe position.
After approx.
5 seconds, the positioner is
automatically reset and the RAM is
reinitialized.
If the error persists even after the positioner
has been reset, the device will need to be
returned to the manufacturer for repair.
Error during the table processing, pointing
to an error in the working data (RAM).
The actuator is moved to the safe position.
After approx.
5 seconds, the positioner is
automatically reset and the RAM is
reinitialized.
If the error persists even after the
positioner
has been reset, the device will need to be
returned to the manufacturer for repair.
Error when verifying the checksum of the
configuration data (RAM).
The actuator is moved to the safe position.
After approx.
5 seconds, the positioner is
aut
omatically reset and the RAM is
reinitialized.
If the error persists even after the positioner
has been reset, the device will need to be
returned to the manufacturer for repair.
Error in the processor function registers
(RAM).
The actuator is moved to
the safe position.
After approx.
5 seconds, the positioner is
automatically reset and the RAM is
reinitialized.
If the error persists even after the positioner
has been reset, the device will need to be
returned to the manufacturer for repair.
Internal
error.
The actuator is moved to the safe position.
After approx.
5 seconds, the positioner is
automatically reset.
If the error can be reproduced and occurs in
the same position after resetting, the device
must be returned for repair to the
manufacturer.