- 112 -UMC100-FBP
Universal Motor Controller
UMC100-FBP
Technical Description
FieldBusPlug / Issue: 03.2012
Indicator Code Source / Root Cause Possible Cause / Suggested Ac-
tion
Overload Power 35 Load side mechanics The motor load is too high. Check if
the load is blocked or tight.
Voltage Out of Spec 36 Load side The supply voltage is too low or too
high. Check the motor supply.
THD Warning 37 Supply side The harmonics on the supply side
are too high. Check your network.
Num Starts Overrun 43 Application The motor was started too frequent.
Just One Start Left 44 Application The motor was started too frequent.
Cooling time running 45 Process, Load side Motor was tripped due to thermal
overload. Restart is possible after
cooling time is over
Parameter out of range 54 Electronics, Configuration Someone tried to write a parameter
which is outside the specifications
Check the parameter number that
is causing the problem and change
the value.
When writing parameters from
within a PLC check your program.
Torque open in intermedi-
ate position
64 Actuator mechanics Tight operation or wiring problem.
Torque close in intermedi-
ate position
65 Actuator mechanics Tight operation or wiring problem.
Pos. open and closed at
same time
66 Actuator mechanics Wiring / position switch problem
End pos. open not left
within specified time
67 Actuator mechanics Wiring / position switch problem
or wrong adjustment of position
switch.
End pos. closed not left
within specified time
68 Actuator mechanics Wiring / position switch problem
or wrong adjustment of position
switch.
End position open with-
out command
69 Actuator mechanics Wiring / position switch problem.
End position closed with-
out command
70 Actuator mechanics Wiring / position switch problem.
Left pos. open without
command
71 Actuator mechanics Wiring / position switch problem.
Left pos. close without
command
72 Actuator mechanics Wiring / position switch problem.
Motor operation hour
exceeded
74 Load side mechanical Max. motor operation hours
reached.
Perform motor maintenance
Reset counter
Wrong password 76 Electronics
Line frequency out of
range
77 Supply side Check supply
Wrong phase sequence
(reversal)
78 Supply side,
Load side
Phase order is not L1/L2/L3.