- 85 - UMC100-FBP
Universal Motor Controller
UMC100-FBP
Technical Description
FieldBusPlug / Issue: 03.2012
Control Function Actuator 1 - 4
Use this function in a feeder that requires the operation of an actuator that opens/closes e.g. a valve.
Please note that the actuator operation mode is not able to keep a valve at a certain setpoint.
The voltage dip function is not supported and checkback via DIO is not supported in
these control functions.
Set the following parameters as listed here:
- Inv DI start input = No
- Inv DI stop input = No
- Inching DI start input (Jog) = Yes
- Multifunction 0/1 = Off
- Checkback: Current or Simulation (test purposes only)
- Adjust Time Limit Actuator
L1, L2, L3
3
Contactor
Supply
(e.g. 230VAC)
K1
DOC DO0 DO1 DO2
24VDC
10 11
5 7 8 9
24VDC
DO3
12
13 14 15 16 17 18
DI0 DI1 DI2 DI3 DI4 DI5
UMC100
UMC-
PAN
Fieldbus
Plug
0V
I
Lim
Open
Close
GND
(24VDC)
K2
k1
k2
K1=Open
K2=Close
Limit
Open
Limit
Closed
M
Torque
Open/
Closed
Control function = Actuator 2 (Basic circuit)
The control functions Actuator 1, 2, 3 and 4 provide different use of and reaction to the limit switches
“Closed” and “Open” as well as the torque switches. The switches must be connected in a predefined
manner to DI0, DI1 and DI3.
Optionally terminals named 24VDC Out (12) or DO2 can be used as a fault output