- 86 -UMC100-FBP
Universal Motor Controller
UMC100-FBP
Technical Description
FieldBusPlug / Issue: 03.2012
Overview:
Control function Open <-> Closed
Torque open Limit open Limit closed Torque closed
Actuator 1 - Stop Stop -
Actuator 2 Stop Prepare Prepare Stop
Actuator 3 - Stop Prepare Stop
Actuator 4 Stop Prepare Stop -
Acutator 1
Open and Closed position via limit switches
Usage with limit switches
DI0
13
24V
12
DI3
16
DI1
14
Open
Torque
Open,
Closed
Closed
2CDC 342 020 F0205
Limit switches
DI0: Motor off, start only in Closed direction
DI1: Motor off, start only in Open direction
DI3: Fault: motor stops
Remark:
•Torque signals are not necessary but can
be used for surveillance.
•After switching off the motor continues
to run for some milliseconds due to its
rotating mass. Adjustment of the Closed
and Open limit switches is necessary to
achieve the correct end positions.
Usage without torque switches
DI0
13
24V
12
DI3
16
DI1
14
Open Closed
2CDC 342 021 F0205
Limit switches
DI0: Motor off, start only in Close direction
DI1: Motor off, start only in Open direction
Remark:
Connection if torque contacts are not avail-
able