EasyManua.ls Logo

ABB UMC100-FBP - Control Function Pole-Changing Starter

ABB UMC100-FBP
158 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
- 82 -UMC100-FBP
Universal Motor Controller
UMC100-FBP
Technical Description
FieldBusPlug / Issue: 03.2012
Control Function Pole-Changing Starter
Use this function in a feeder that requires a two-pole or dahlander motor to start-stop in one direction of
rotation.
•Relay output DO0 is used by the control function to start the motor at speed one
•Relay output DO1 is used by the control function to start the motor at speed two
•Optionally DI0 can be used for contactor checkback supervision
•Optionally DI4/D3 can be used to start the motor at speed one/two and DI5 to stop it
•Optionally terminals named 24VDC Out (12) or DO2 (9) can be used as a fault output
The voltage dip function is not supported in this control function
Set I
e2
according to the motor nameplate
The following diagram shows the UMC wired for two-pole operation. A signal lamp is connected to DO3
which serves as a fault output. The main contactor is connected to DO0 and DO1. Two auxiliary contacts
are used for contactor checkback monitoring. The motor can be started locally via DI4 (speed one) or DI3
(speed two) and stopped via DI5. The remaining digital inputs can be freely used.
Two-Pole Motor
L1, L2, L3
M
3
Contactor
Supply
(e.g. 230VAC)
K81
DOC DO0 DO1 DO2
24VDC
10 11
5 7 8 9
24VDC
DO3
12
13 14 15 16 17 18
DI0 DI1 DI2 DI3 DI4 DI5
UMC100
UMC-
PAN
Fieldbus
Plug
0V
I
Lim
Speed1
Stop
GND
(24VDC)
K91
k91k81
K81=spped one
K91=speed two
U1
V1
w1
U2
V2
w2
Speed2
k81
k91
Circuit diagram of the UMC for controlling a two-pole motor. The checkback contacts k81/k91 are