- 134 -UMC100-FBP
Universal Motor Controller
UMC100-FBP
Technical Description
FieldBusPlug / Issue: 03.2012
Function Block Related Parameters
Aux Input Block
In the standard built-in applications the inputs of this function block are connected to the digital inputs of
the DX1xx module (see section 'Using Expansion Modules').
Param-
eter
Number
Parameter Name Description, Explanation Options Adjustable
via
51 - 56 Aux inp 1-6 ack
mode
Definition of the fault reset
behavior
Manual Reset (0)
Auto Reset (1)
All
57 - 61 Aux Inp 1-6 reac-
tion
Definition of the input
function
NC: Normally closed
NO: Normally open
Disabled (0)
Fault (NC) Motor in On/Off (1)
Fault (NO) Motor in On/Off (2)
Fault (NC) Motor in On (3)
Fault (NO) Motor in On (4)
Warning (NC) Motor in On/Off (5)
Warning (NO) Motor in On/Off (6)
Warning (NC) Motor in On (7)
Warning (NO) Motor in On (8)
All
63/64
65/66
67/68
69/70
71/72
73/74
Aux Inp 1-6 mes-
sage Line 1/Line 2
Message text line 1 and
line 2
Free text with 8 characters
for each line. Default: „Aux
DIx“ with x=1...6
DTM,
UMC100-
PAN
75 - 80 Aux Inp 1-6 delay Input delay time in mul-
tiples of 100ms
0 ... 255 in multiples of 0.1s
Example: A value of 5 means
500ms
All exclud-
ing GSD-
PDQ22