The low current function is triggered when the motor current falls below a desired level. The function
detects loss of suction for pumps, broken belt for conveyors, loss of airflow for fans, broken tools for ma-
chines etc. Such states do not harm the motor but early diagnosis helps to minimise the extent of dam-
age to the mechanical installation and subsequent loss of production.
The motors on underload draw mainly the magnetising current and a small load current to overcome fric-
tional losses. Therefore, the other reason to isolate the motors on underload is to reduce the reactive load
on the power system network.
The low current function signals a warning when the motor current falls below the warning level for a
configurable period of time, after motor start-up. The low current function creates a trip when the motor
current falls below the trip level for a configurable period of time, after motor startup.
Block Diagram:
&
I/Ie[%]
I<Ilcwl
Tlcwd
Low Current
Warning
After Start-up
I<Ilctl
& Tlctd
Low Current
Trip
Signal flow of the low current protection function.
Example:
The diagram above shows an underload situation of the motor after the startup time is over (T1). At T2 the
motor current falls below the undercurrent warning limit I
ucwl
. After the undercurrent warning delay time
t
ucwd
an undercurrent warning is set.
Then at T3 the current also falls under the undercurrent trip level I
uctl
but only for a period shorter than the
specified undercurrent trip delay time t
uctd
. Therefore no trip happens. At T4 the current falls again under
the low current level and stays there. Therefore a trip is released and the motor stopped.
[%]
t
I/I
e
I
lctl
I
lcwl
I
e
T1
I
SE
---------------------------------------/===========================================================
-------------------------------------------------------------------------------/===================
T2
T3
t
lcwd
t
lctd
t
lctd
T4
Trend diagram of the motor current over time showing the function of the low current protection
function with the related parameters.
Relevant Parameters
•Undercurrent Trip Level
•Undercurrent Trip Delay
•Undercurrent Warning Level
•Undercurrent Warning Delay
I
lctl
: Low current trip level
I
lcwl
: Low current warning level
t
lctd
:Low current trip delay
t
lcwd
:Low current warning delay
I
e
: Nominal current
I
SE
: Current defining the end of the
start-up period