- 57 - UMC100-FBP
Universal Motor Controller
UMC100-FBP
Technical Description
FieldBusPlug / Issue: 03.2012
U
Dip
Restart
Level
Dip
Level
UMC Relay Out
Undervoltage situation
Dip Autorestart Window
DIP signal at
digital input
Dip
Auto-
restart
Delay
DIP Duration
Case b: The low voltage situation takes longer than the configured 'Dip Autorestart Window' which
means the UMC switches off the relay output. But the low voltage situation is shorter than the configured
'Dip Duration' so the motor gets started automatically after an optional restart delay time (Parameter 'Dip
Autorestart Enable=On). Otherwise it stays off.
Case c: The low voltage situation takes longer than the 'Dip Duration' time. Therefore an error is gen-
erated as soon as the dip duration exceeds the configured dip duration time.
U
Dip
Restart
Level
Dip
Level
UMC Relay Out
Undervoltage situation
DIP signal at
digital input
Dip Duration
UMC Voltage
DIP Error