67
9.3.2 Maintenance in the low voltage compartment
9.3.2.1 Checking of correct operation of the
protection release
Make the plant you want to work on safe (follow
the plant safety regulations).
Move the three-position disconnector to EARTH
position and close the circuit breaker.
Withdraw the protection release from the fixed part
fixed onto the door of the low voltage
compartment.
Using current and volumetric test boxes, carry out
injections to check perfect operation of the
protections themselves.
Note: To check operation of the protection releases,
refer to the operating manual of the protection
provided by the manufacturer.
9.3.2.2 Cleaning and checking the auxiliary
connections
Make the plant you want to work on safe (follow
the plant safety regulations).
Move the three-position disconnector to EARTH
position and close the circuit breaker.
Open the miniature circuit-breakers (Figure 115)
positioned inside the low voltage compartment to
remove the auxiliary power supply to the panel.
Carry out a visual inspection on all the cabling,
terminal boxes (Figure 115) and check for any
presence of dirt.
Manually check correct insertion of the cabling in
the terminal box.
9.3.2.3 Measuring the insulation resistance of the
auxiliary circuits
Make the plant you want to work on safe (follow
the plant safety regulations).
Move the three-position disconnector to EARTH
position and close the circuit breaker.
Open the circuit-breakers (Figure 115) positioned
inside the low voltage compartment to remove the
auxiliary power supply to the panel.
From one of the circuit-breakers (Figure 115)
disconnect the wires on the internal side of the
panel.
Using a Megger instrument, measure the
resistance between the phase involved and the
conductive electric part (switchgear structure). The
value must not be less than 2 MOhm and in any
case constant over time.
Repeat the operation for the number of circuits
(circuitbreakers) inside of the panel (110 V dc, 220
V ac, etc).
Replace the connections and put the panel into
service.
Figure 115: Low voltage compartment.