Installation and maintenance instructions UniGear type ZS2 UniSafe-36 1YTW571780-012 Rev:E 01-2005 en Page: 16 of 25
2.7 Cables termination
The cables must have been earthed before access to cables compartment. Removal of the horizontal bottom
plate in the breaker compartment and/or removal of the rear-cover allows access to cables compartment.
Please consider that some commissioning tests (part 3) are done with the power cables disconnected.
Fig:2.7.1
Fig 2.7.2
Fig:2.7.3
Fig: 2.7.1 2.7.1 2.7.3 2.7.3 2.7.2
Cable comp. width,mm 1000 1000 1200 1200 2000
Cu conn. bars, Cu 2x40x10 2x80x10 4x40x10 4x80x10 4x80x10
Typical Cable lugs
DIN46235, sqmm/ph
2x1x400
2x1x630
4x1x400
4x1x630
4x1x630