Installation and maintenance instructions UniGear type ZS2 UniSafe-36 1YTW571780-012 Rev:E 01-2005 en Page: 6 of 25
2 INSTALLATION INSTRUCTION
!
CAUTION! Make sure that the cubicle can not be dropped or tilted during unpacking,
transportation or assembly.
CAUTION! The encapsulating sheet steel of cubicles may have sharp edges inside and on the roof.
2.1 Floor
Check the floor regarding openings for the cables according to figure 2.1.1 and/or 2.1.2
Check the floor level. The deviations in height for the supporting surface to the cubicles must be less than
2mm/m. Otherwise the cubicles will require spacers to get a proper aligning.
Figure 2.1.1 Floor layout view, typical
D
CL
CR
Rear cover depth,
Lateral clearance,
Rear clearance,
52 ... 140mm mm
600 (min. 100) mm
600 (min. 100) mm