11
Automatic configuration
Auto configure is the first step to take
after the panel is initially energized. This
function recognizes the electrical system,
then automatically sets all the system
parameters: system voltage, frequency,
and phase sequence.
Follow the steps in the figure on the HMI
to run auto configure. The ATS must have
at least one source available to complete
this step.
To put your ATS into Auto mode, confirm
the slide switch is in “AUTO” before the
enclosure door is closed. This slide switch
overrides the Auto/Manual mode set from
the HMI. To place the ATS controller in
AUTO mode through HMI screen, set
"Automatic mode" to "ON" in the
operations menu.
Confirm the ATS is in Auto mode by
validating that the “AUTO” LED above and
to the right of the LCD screen is solid
green.
Confirm Automatic Operation
Fig. 4
Fig. 3
S1 Connected to Load
Load Current
393 A
11:06
60s
G
Override S1 Fail
TruONE ATS
S
ystem Overview
S
1 Ok Not Ok S2
Operation Parameters Measurements
AboutTestSettings
TruONE AT
S
1.
2.