Zenith ZTS(D) 30-1200A ATS, QUICK START USER MANUAL
—
Warnings
LCD
Touch
Message Reason
Voltage sources are not synchronized
Voltage Not Calibrated Calibration data in power module is invalid or unavailable
Current Not Calibrated Calibration data in current measurement module is invalid or unavailable
Pole temperature warning Measured pole temperature is near the alarm level
Control Retry Failed transfer sequence retry activated
Auto Control Disabled Device is in manual operating mode
Local Bus Module heartbeat error.
Check connection. Can be cleared using "Alarm Reset".
Configuration Configuration session ports are open
Clock capacitor charging Real time clock is not yet operational, date & time setting is disabled as
long as this warning is active. Clock capacitor is charged from source
—
Table 7 Warnings-list in level 3 and 4, LCD and touch control interfaces