23
Message Fault Action
  Check the power source
 
from the value of parameter “Phase
sequence“
Connect the phases according to the
configuration
 
set in parameters “Drop-out frequency,
upper threshold“ and “Drop-out
frequency, lower threshold“
Check the correlation between power
source and device configuration
Frequency Difference Frequency difference of voltage

phase monitor is on
Alarm is active and transfer operations
disabled as long as the frequency
difference is above the accepted level
High current alarm Measured current is higher than ten
times the nominal value
Alarm is active and transfer operations
disabled as long as the high current
status remains
Open I failure, Alarm
LED blinking
Switch transfer from position I to O or
II failed
Reset alarm by pressing Auto button or
via menu page Operation / Alarm Reset
Close I failure, Alarm
LED blinking
Switch transfer to position I failed Reset alarm by pressing Auto button or
via menu page Operation / Alarm Reset
Open II failure, Alarm
LED blinking
Switch transfer from position II to O or
I failed
Reset alarm by pressing Auto button or
via menu page Operation / Alarm Reset
Close II failure, Alarm
LED blinking
Switch transfer to position II failed Reset alarm by pressing Auto button or
via menu page Operation / Alarm Reset
Switch position alarm,
Alarm LED on
More than one switch position
indication inputs are activated
Switch service needed
Pole temperature
alarm
Measured pole temperature is too high Switch service needed
Contact wear alarm Switch contact wear is near the limit
that requires maintenance
Switch service needed
Ekip Com Hub Alarm Ekip Com Hub failure Check configuration
HMI Not Compatible
Firmware versions of HMI and device
are not compatible to be used together
Check current versions and update
compatible versions
Local bus Communication between HMI and
switch controller is off
Check connection
Ethernet
disconnected
Ethernet module not connected Check connection
Fire Fighting Fire fighting input activated
Alarm is active and disables transfer
operations as long as the input is active
Control Voltage
Failure
Control voltage dropped during switch
control
Check power source
Control Voltage Low Switch control voltage is below the
minimum
Check power source
Configuration Error Invalid configuration Check parameter values
  Check configuration file
Ekip Com Hub Alarm Ekip Com Hub failure Check configuration
HMI Not Compatible
Firmware versions of HMI and device
are not compatible to be used together
Check current versions and update
compatible versions
Table 6 Alarms-list in level 3 and 4, LCD and touch control interfaces