24
BATTERY OPERATION
During power failure....
The operator and devices connected will operate normally. The red LED starts
to blink.
8.0 V 10.5 V
WHEN BATTERY VOLTAGE DROPS UNDER
The operator stops Low-energy state:
The door is opened manually
and the operator closes door.
12 V Full battery backup; The operator and devices connected will operate during
a power failure. The operation time depends on number of openings and the current
draw of the devices fitted.
2.0 V 13.0 V
BATTERY VOLTAGE
When power failure ends....
The red LED stops blinking. If the operator stays in low-energy state, one
manual opening is required to re-enegise the operator to chosen program
selector mode.
When battery backup is chosen, the battery is checked by the operator and the
following should be noted:
The test made by the operator: The battery is loaded with 0.4 A test load for a
30 second period. If the battery voltage drops under 11.5 V, the battery is
found unsuitable => a red LED flashes at the end of the operator indicating this
state.
Battery operation will
not function
The battery is tested if the
voltage rises above 13 V it
is operational.
If the voltage does not rise
above 13 V in 24 hour period,
the battery should be
replaced
The operator tests
the battery