28
ABLOY FIRE DOOR SYSTEM (Not according UL regulations)
The ABLOY DA400 for fire doors with
ABLOY smoke detectors and relays
Max two smoke
detectors
PLEASE NOTE,
LOCK THE DETECTOR
yellowt
yellow
black
black
gray
Locking
circuit
gray
gray
white
blue
black
red
green
SET THE FOLLOWING
CONTROL POINTS:
15 : Battery operation = 1 (Fire door use)
16: Hold open time to minumum
18 : Operation of lock control relay = 1 (The relay doesn't
work in MANUAL-mode)
22: Lock control relay hold time = 1s.
Also adjust the lock control relay hold time to a minimum !!
AUTO
OPEN
FUNCTION
When the detector reacts, the relay 453 switches on. Then the negative (-) is disconnected
from the Battery adapter(connector 6)causing the operator to change to the MANUAL position,
regardless the position of the programming switch. Also in case of the power failure the
operator changes automatically to the MANUAL position, if the fire door use has been selected
in the control points for battery function. In MANUAL position the door always closes after
the preset delay.
In case of fire -> the door closes
Power failure -> the door closes (battery powered)
IF USING DA400 IN FIRE DOORS,
ALWAYS CHECK THE LOCAL FIRE REGULATIONS!!!
ABLOY 8400
ABLOY
MOTOR LOCK
scandinavian type
Diagram
L1
C6
C5
A4
A3
L2
L1
C6
C5
A4
A3
L2
yellow
DA400
18
17
12
18
13
15
Red
Black
Blue
Yellow
3
19
25
21
23
6
7
8
9
Battery
adapter
950596
Red
White
Blue
Black
1
2
3
4
NO
POWER
ALARM
BATTERY
ALARM
NO
C
C
Relay 453
N.C.
red
Relay 453
N.C.
red