EasyManua.ls Logo

Absolute ABS-1500 - Cleaning the Burner Assembly; Cleaning the Siphon

Absolute ABS-1500
74 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Absolute Boilers ABS 1500-2000-2500-3000-4000
70
Max. 70 PSI air pressure to clean burner
11.1.5 Cleaning the burner assembly
CAUTION
Turn electrical o, then ensure gas has been shut o at the main shut o valve. Next purge all gas in the system
as per code. The burner may be hot, allow enough time to allow the boiler to cool before removing the burner tube.
Upon removal of the burner tube, inspect it for any damage to the woven mesh and ensure no damage has been done
to the tube from heat. If the burner is in good condition, clean the burner assembly by using compressed air only –
between 30 – 70 psi [2-5 bar] with the nozzle positioned a min of 3/8” [10mm] away and towards the face of the burner.
If there is any damage to the mesh or tube, the burner must be replaced. Check the retaining bolts are tight. If the
burner is removed from the front plate ensure burner-retaining screws are tight on re-assembly
11.1.6 Cleaning the siphon
Remove the complete siphon (located underneath condensate
collector beneath the ue connection). Remove siphon, clean and
rell with clean water and re-t.
Fig. 35 – Condensate siphon assembly

Table of Contents