Absolute Boilers ABS 1500-2000-2500-3000-4000
73
Description Schedule
System pressure Monthly
Control functioning Monthly
Seals or evidence of leaks Monthly
Unobstructed combustion air supply, no chemicals, garbage, gasoline, combustible
materials, ammable liquids are stored near the boiler.
Monthly
Check for water on the oor around relief, vent and other parts and piping of the
water system
Monthly
Check operating limits for correct operation Semi-annually
Ensure neutralization system is working Semi-annually
Check exhaust terminals for ice, snow or debris buildup Monthly
Check air inlet lter ( Shall be done weekly if unit is operating in a construction zone) Monthly
Check and test pressure relief safety valve Annually
Test temperature Hi limit functions Annually
Checks for system leaks Annually
Check all auxiliary and other safety limit for function and correct operation.
Monthly
Check system water quality refer to the water quality manual for specics Monthly
Check pump operation Annually
Check fuel lines for leaks Annually
Check combustion Annually
Check control settings Annually
Clean combustion chamber Bi-Annually
Clean condensation collector and siphon Annually
Clean Gas inlet lter Semi-annually
12.Maintenance Schedule