Page 14 Data : 01.03.2016
8 Activation of LIS control unit
Important: Once the load measurement and evaluation
function has been activated, it cannot be deactivated
again.
To activate the load measurement and evaluation func -
tion of the LIS control unit, select parameter 3.0 using
the ”up” button. Press the ”enter” button for some time
and the system will request you to enter a PIN no. Enter
”0055”. Press ”enter” a gain. The unit will be re- initiali-
zed and activation will be completed.
_________________________________
9Disposal
ABUS products are designed with a view to recycling
and have a modular structure which facilitates environ-
mentally compatible disposal when they are no longer
required.
The electronic components may be disposed of at spe-
cial disposal sites in accordance with the applicable lo-
cal regulations.
_________________________________
10 LIS – SE parameter list
Para-
meter
Range Unit Designation Remarks
CodE Reading out load population recorder
“Menu level 1”
Only available if LKS has
been enabled.
CODE 2223
P0.0 0 – 100 t Total load capacity
Input not required
P0.1 0–80 t Display and input Load capacity, hoist 1
P1.1 0–17 Display and input Motor type
in accordance with table
P1.2 0–97,999 Display and input W inding resistance
P1.3 Display and input Current correction factor
P2.1 Display and input Unit setting, precision lift
P2.2 Display and input Unit setting, main lift
P2.3 Unit setting t load ”Teach–in 1”
P2.4 Unit diagnosis parameter CODE 1443
P3.0 t Display mode ”Load indication”
P3.1 kW Display mode ”Rotating field power”
P3.2 t Display mode ”Load indication”
P3.3 A Display mode ”Conductor current”
P3.4 V Display mode ”Supply voltage”
P3.41 V Network voltage analysis
P4.0 0–110 % Display and input second shut- down point
only active with signal at
input EA
P4.1 0–110 % Display and input Overload shut–down, hoist 1
P4.2 0–110 % Display and input Part–load s witch 1
P4.3
no function
P4.4 Operationontwinhoist
no function