EasyManua.ls Logo

Abus LIS-SE - Standard Settings; Standard Settings Procedure

Abus LIS-SE
37 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Page 22 Data : 01.03.2016
12 Standard settings
Important: Steps 1a* and 1b* only apply if the load population recorder is activated.
Otherwise, start with step
1.
0
flashing
No.
Key Description Display
1a* Enter Code” appears on display CodE
1b* Enter
briefly
”P–Nr.” appears on display P–nr
1 Enter Press until ”P–Nr.” a ppears on display P–nr
2 Enter press for about 1 sec. and release. The display is: 0 000
3
+
Enter
Enter PIN No. from left to right.
After entering the last digit, press ”Enter” until P 0.0 appears on the display
0055
flasching
4 The unit is now on level 2 ( parameter level) P0.0
5 select parameter P 0.1 load capacity, hoist 1 P0.1
6 Enter the load capacity currently stored appears on display (in t) 3.20 e.g
7 enter required value for load capacity, hoist 1, in t 5.00 e.g.
8 Enter display flashes briefly; load capacity, hoist 1, is stored; the display is: P0.1
9 select parameter P 4.1 overload shut–down, hoist 1 P4.1
10 Enter 110 or the value currently stored appears on display 110
11 enter required value for overload shut–down, hoist 1, in % of load capacity,
hoist 1
100 e.g.
12 Enter P 4.1 appears on display; value is stored P4.1
13 select parameter P 4.0 Second shut- down point P4.0
14 Enter 0 or the value currently stored appears on display 0
15 enter required value e.g. 40 % for part load switch 1
( in % of load capacity, hoist 1 see parameter 0.1)
.
If input EA is not used, this setting is of no importance.
40 e.g.
16 Enter P 4.0 appears on display; value is stored P4.0

Related product manuals