Heat pumps AIR / WATER
Operation manual 24
displayed, the desired value is given by the value entered in the white input field
on the main page.
The required temperature in the room is entered into the white field of the Submit column. In
the case of ST selection (Chap. 3.2.6 on page Chyba! Záložka není definována.) it is possible
to enter the water temperature in the tank. If the tank is not fitted, the temperature of the water
returning from the heating system (reverse) is entered. In the case of the Equitherm or
AcondTherm control selected, this value is calculated from the outside temperature, or from the
room temperature, and cannot be changed manually.
After entering the value, the change must be confirmed by pressing the ENTER key or by
clicking the arrow in the right part of the white input field.
Acond Therm® control normally maintains the set temperature in the room
with a tolerance of +/- 0.5°C. This tolerance is exceeded only in exceptional
cases (e.g. after restarting the system, after changing the desired temperature,
after ventilation, etc.).
When selecting service water preheating, the temperature of 45°C used to heat service water
is maintained in the tank in the summer.
When Antisepsis is enabled, the boiler is disinfected once a week by heating to 60°C.
Antisepsis can also be triggered once by clicking on the "Antisepsis start" sign.
When selecting Fan attenuation, it is possible to specify the time when the fan speed will be
reduced due to the noise of the heat pump. In the summer, when the outdoor temperature
exceeds 17°C, the speed is automatically reduced.
Figure 7 Service water - Antisepsis