77
Communication address description
Speed command of
RS485
100
Setting Range 0 ~ 4
Default Value 3
0 : Normal
1 : Forward run
2 : Reverse run
3 : Stop
4 : Fail mode reset
Note : 1.Fail mode reset by writting address 100 content=4.
2. Speed command is CD00, or using CF1/CF2/CF3 terminal to
select 2
nd
~8
th
speed (CD22~CD24, CD47~CD50).
Frequency data
output for RS485
101
To know output frequency, using function 03H to read address 101
content.
Unit 0.1HZ
Model code
CD96
To know model code, using function 03H to read address 96(06H) con-
tent.
Version of program
CD97
To know version of program, using function 03H to read address
97(61H) content.