EasyManua.ls Logo

Advanced Energy Thyro-PX - User Manual

Advanced Energy Thyro-PX
109 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
Loading...
Thyro-PX
®
Power Controller
User Manual
April 2020 57010148-00G

Table of Contents

Questions and Answers

  • M
    Marvin SmithSep 8, 2025
    What does it mean if the green ON/ READY LED is not lit on the Advanced Energy Thyro-PX Controller?
    • J
      Jesse AdkinsSep 8, 2025
      If the green ON/ READY LED is not lit on the Advanced Energy Controller, the auxiliary 230 VAC or 24 VDC supply is faulty.
  • J
    John HarrisonSep 12, 2025
    What to do if my Advanced Energy Controller has no load current?
    • N
      Nathan SextonSep 12, 2025
      If your Advanced Energy Controller shows no load current, verify the following: * The supply voltage of the A70 control device is within the range of 90 VAC to 265 VAC, or X3.1 and X3.2 are at 24 VDC. * The setpoint is available and active. Check the total setpoint (effective total) using the display or software, or measure the setpoint on X52.2 and X52.5. * Parameters of the control characteristic of the respective analog input are correct. * For 1PX and 2PX units, verify that the reference phase is connected. Also, check if parameters Iemax, Uemax, and Pmax are set too small, or if controller parameters Ti or Kp are set too large. For type 1PX, check if the load is broken or disconnected.
  • M
    Matthew ClaytonSep 12, 2025
    Why are no LEDs lit on my Advanced Energy Thyro-PX?
    • C
      Christopher AndersonSep 13, 2025
      If no LEDs are lit on your Advanced Energy Controller, it could be due to several reasons. First, check for a missing customer-supplied power supply for the A70 control device. Then, ensure that the voltage at terminal X1.1 and X1.2 of the A70 control device is within the range of 90 VAC to 265 VAC, or that X3.1 and X3.2 are at 24 VDC. Also, verify that fuses F2 and F3 on the A1, A3, and A5 controller cards are not open and that the semiconductor load fuses are not open. For transformer loads, the phase angle of the first half-wave might need to be optimized. Begin with a phase angle (phase angle 1) = 60 degrees, and slowly increase until the inrush current is minimized. Check for missing power supply.
  • A
    Andrea LoganSep 14, 2025
    What causes the thyristors to be set to full scale on my Advanced Energy Thyro-PX Controller?
    • K
      Kathryn KiddSep 15, 2025
      If the thyristors on your Advanced Energy Controller are set to full scale, check the control characteristic of the respective analog inputs. Also, controller parameters Ti and Kp might be set too small, or parameters Iemax, Uemax, and Pmax may be set too large, or the load current may be too small. If no load is connected, the voltage will be higher than 0 V. A load must be connected to troubleshoot this condition. Additionally, check the thyristor resistance between L1 and T1, L2 and T2, L3 and T3. If the resistance is greater than 100 ?, the thyristor is not damaged.
  • N
    Nathan SanchezSep 16, 2025
    How to troubleshoot other malfunctions in Advanced Energy Thyro-PX?
    • B
      bryanmarkSep 16, 2025
      To troubleshoot other malfunctions in your Advanced Energy Controller: * Evaluate the fault log entries using the Thyro?Touch display or the Thyro-Tool Pro software. * Check the parameters. * Check the wiring of the unit. * Check the number of controlled phases (parameters). * Eliminate the fault indicated by the fault relay. * Visually verify correct operation by replacing the loads with appropriately rated incandescent lamps.

Advanced Energy Thyro-PX Specifications

General IconGeneral
ManufacturerAdvanced Energy
Input Frequency Range47 - 63 Hz
CategoryController
CommunicationEthernet
Output Current RangeSee Output Current
ProtectionsOvercurrent, Overvoltage, Overtemperature
Communication InterfaceRS-485, Ethernet
DimensionsVaries by model
WeightVaries by model

Related product manuals