EasyManua.ls Logo

Advantech Adam 4000 Series - Page 100

Advantech Adam 4000 Series
398 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Command Set
4-16 ADAM 4000 Series User's Manual
ADAM-4017+ Command Set
Command Syntex
Command
Response
Syntex
Command Description
Command
Example
Command
response
Example
%AANNTTCCFF(cr)
TT : All channel
input range code.
CC : Baud rate code,
03 : 1200
04 : 2400
05 : 4800
06 : 9600
07 : 19200
08 : 38400
09 : 57600
0A : 115200
FF : reference
command
description
!AA (cr) TT : Initial Value FF
(not use
If change FF to XX ,
All channel input
range be seted to XX
XX : +/-10V : 0x08
+/-5V : 0x09
+/-1V : 0x0a
+/-500mV : 0x0b
+/-150mV : 0x0c
+/-0~20mA: 0x0d
+/-4~20mA: 0x07
FF : setting
7 6 x x x x 1 0
bit 7 : Integration time
0 : 50ms(60HZ)
1 : 60ms(50HZ) bit
6 : checksum
0 : disable
1 : enable
bit 1,0 : Data Format
00 : Engineer unit
%0105FF06-
00(cr)
!05(cr)
#AAN(cr)N: 0 ~ 7 >(data)(cr)data
: snnnnnn
s : + or
-n : digit or dot
Read Analog Input from
Channel N (N from 0 - 7)
When over range the (data)
will show>+999999(cr)
When under range the (data)
will show>-000000(cr)
#035(cr) >+09.789(cr)
#AA(cr) >(data0)(data1-
)(data2)(data3-
)(data4)(data5)
(cr)data
0 ~ 5: snnnnnn
s : + or
-n : digit or dot
Read Analog Input (for all 8
ch)
When over range the (data n)
will show>+999999(cr)
When under range the (data n)
will show>-000000(cr)
#03(cr) >+05.000-04.9-
00 +100.23-
089.32+09.123
+123.45-09.13-
4(cr)
(channel 5 be
disable)
$AA0Ci(cr)
i: 0 ~ 7 channel
number
!AA(cr) Gain error calibrate of
assignment channel, User
have to input the external
standard source for calibrating
process
$050C7(cr) !05(cr)

Table of Contents