Command Set
4-20 ADAM 4000 Series User's Manual
ADAM-4018+ Command Set
Command Syntex
Command
Response
Syntex
Command Description
Command
Example
Command
response
Example
%AANNTTCCFF(cr)-
TT : All channel
input range code.
CC : Baud rate code,
03 : 1200
04 : 2400
05 : 4800
06 : 9600
07 : 19200
08 : 38400
09 : 57600
0A : 115200
FF : reference
command
description
!AA (cr) TT : Initial Value FF (not use)
If change FF to XX , All
channel input range be
seted to XX
XX : +/-0~20mA: 0x06
+/-4~20mA: 0x07
J type : 0x0
K type : 0x0f
T type : 0x10
E type : 0x11
R type : 0x12
S type : 0x13
B type : 0x14
FF: setting
7 6 x x x x 1 0
bit 7 : Integration time
0 : 50ms (60 HZ)
1 : 60ms (50 HZ)
bit 6 : checksum
0 : disable
1 : enable
bit 1,0 : Data Format
00 : Engineer unit
01 : % of FSR
10 : Two's complement
%0105FF06-
00(cr)
!05(cr)
#AAN(cr)N: 0 ~ 7 >(data)(cr)data
: snnnnnn
s : + or
-n : digit or
dot
Read Analog Input from
Channel N (N from 0 - 7)
When over range the (data)
will show>+999999(cr)
When under range the (data)
will show>-999999(cr)
When burn-out the (data) will
show>+888888(cr)
#035(cr) >+09.789(cr)
#AA(cr) >(data0)(data1-
)(data2)(data3-
)(data4)(data5)
(cr)
data0 ~ 5 :
snnnnnn
s : + or
-n : digit or dot
Read Analog Input (for all 8
ch)
When over range the (data n)
will show>+999999(cr)
When under range the (data n)
will show>-999999(cr)
When burn-out the (data) will
show>+888888(cr)
#03(cr) >+05.000-04.9-
00 +100.23-
089.32
+09.123
+123.45-09.13-
4(cr)(channel 5
be disable)