4-100 ADAM 4000 Series User's Manual
Command Set
4018M
@AAACSDHHHHTEIIII
Example command: @EFA0020400020100(cr)
response: !EF(cr)
The command sets channel 0 of the analog input data logger at
address EF as such:
high alarm limit = 10.24
low alarm limit = 2.56
The response indicates the command was received.