Chapter 4 Command Set 4-
101
4018M
Chapter 4
@AABC
Name Read Alarm Limit
Description Request the alarm limits for the specified channel in the analog
input data logger at address AA.
Syntax @AABC(cr)
@ is a delimiter character.
AA (range 00-FF) represents the 2-character hexadecimal
address of an analog input data logger.
B identifies the Read Alarm Limit command.
C represents the channel index. Its value is from 0 to 7.
(cr) is the terminating character, carriage return (0Dh).
Response !AASDHHHHTEIIII
! is a delimiter character indicating a valid command was
received.
AA (range 00-FF) represents the 2-character hexadecimal
address of an analog input data logger.
S represents the sign of the high alarm limit. 0 is for positive.
And 1 is for negative.
D represents the decimal point of the high alarm limit. Its value
is from 0 to 5.
HHHH represents the 4-character hexadecimal number of high
alarm limit.
T represents the sign of the low alarm limit. 0 is for positive.
And 1 is for negative.
E represents the decimal point of the low alarm limit. Its value
is from 0 to 5.
IIII represents the 4-character hexadecimal number of low
alarm limit.
(cr) is the terminating character, carriage return (0Dh)

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Advantech Adam 4000 Series and is the answer not in the manual?

Advantech Adam 4000 Series Specifications

General IconGeneral
BrandAdvantech
ModelAdam 4000 Series
CategoryControl Unit
LanguageEnglish

Related product manuals