4-168 ADAM 4000 Series User's Manual
Command Set
4080, 4080D
Figure 4-5
Data format for 8-bit parameter
Not used
Frequency Gate Time
0: 0.1 seconds
1: 1.0 seconds
7 6 5 4 3 2 1 0
%AANNTTCCFF
Name: Configuration
Description: Sets the address, input mode, baud rate, checksum status and/
or frequency gate time for a specified counter/frequency
module
Syntax: %AANNTTCCFF (cr)
% is a delimiter character.
AA (range 00-FF) represents the 2-character hexadecimal
address of counter module that you want to interrogate.
NN represents the new hexadecimal address of the counter/
frequency module. Range is from 00h to FFh.
TT represents the input mode:
50h : counter input mode
51h : frequency measurement mode
CC represents the baud rate code (See table 4-7).
FF is a hexadecimal number that equals the 8-bit parameter
representing the checksum status and frequency gate time. The
layout of the 8-bit parameter is shown in figure 4-5.
Bits 0, 1, 3, 4, 5 and 7 are not used and set to 0.
(cr) is the terminating character, carriage return (0Dh)
Not used
Checksum status
0: Disabled
1: Enabled
Not used

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Advantech Adam 4000 Series and is the answer not in the manual?

Advantech Adam 4000 Series Specifications

General IconGeneral
BrandAdvantech
ModelAdam 4000 Series
CategoryControl Unit
LanguageEnglish

Related product manuals