13
EN
Battery
Autonomy time (for a battery charged 100% and at 25°C)
Linked
battery modules
Autonomy time (nominal load, pf = 0.9 lag.)
D. 1000
D. 1500
D. 2000
D. 3000
With integrated battery
6 min.
5.5 min.
6 min.
3.5 min.
1 extra battery module
31 min.
25 min.
33 min.
18 min.
2 extra battery modules
51 min.
46 min.
59 min.
34 min.
3 extra battery modules
82 min.
69 min.
88 min.
53 min.
4 extra battery modules
100 min.
90 min.
119 min.
69 min.
Rated direct voltage (intermediate circuit)
PROTECT D. 1000 36 V
PROTECT D. 1500 48 V
PROTECT D. 2000 72 V
PROTECT D. 3000 72 V
Float voltage 2.28 Vdc/cell (pre-set to 25°C)
charging voltage temperature dependent
Setting range 2.21 Vdc/cell – 2.31 Vdc/cell
in 0.01V increments
Batt.-charge power (max.) 1.4 Adc (PROTECT D.1000 / D.1500)
1.7 Adc (PROTECT D.2000 / D.3000)
Battery type Valve regulated lead battery (VRLA)
Special type for high-current discharge
PROTECT D. 1000 3 blocks at 12V 9Ah
PROTECT D. 1000 BP 2 belts at 3 blocks at 12V 9Ah
PROTECT D. 1500 4 blocks at 12V 9Ah
PROTECT D. 1500 BP 2 belts at 4 blocks at 12V 9Ah
PROTECT D. 2000 6 blocks at 12V 9Ah
PROTECT D. 3000 6 blocks at 12V 9Ah
PROTECT D. 2030 BP 2 belts at 6 blocks at 12V 9Ah
Recharging times ~ 3h to 90% for internal battery
~9h / ~15h / ~21h / ~27h with 1 / 2 / 3 / 4 battery extension(s)

Related product manuals