3.3 INSTALLING THE BATTERY
The ground or floor must be strong enough to carry the weight of the batteries and/or stands or cabinets in which
they are mounted.
3.4 ENVIRONMENTAL REQUIREMENTS
(EXCLUDING THE BATTERY)
Storage in standard carboard packing box
Temperature: - 25°C to +70°C
Relative humidity: 15% to 90% in the original package.
Maximum storage period: 3 months.
Storage in seaworthy packing
Temperature: - 25°C to +70°C
Relative humidity: 15% to 90% in the original package.
Maximum storage period: 12 months.
For a storage period exceeding the values recommended above, contact the factory in order to know the
required environmental conditions and the maximum storage duration.
Operating
Temperature: 0°C to +50°C
Above 50°C and up to 55°C, the output current must be de-rated (1.25% per °C).
Relative humidity: 20% to 95 % (non-condensing).
Altitude
1000 m
Above 1000 m and up to 4000 m, the output current must be de-rated (7% per 1000 m).