6.6 COMMAND FUNCTION
According to the factory set configuration, your system can have several specific command functions. All these
commands are accessible through the Command function ‘Cmnd’.
The different command functions are:
Manual High rate Charge
Manual Commissioning Charge
Manual floating Charge
Manual Adjustment of Voltage and/or Current
Battery Test Function
Clear History List
Set Display Contrast
Reset Ah meter.
6.6.1 How to Activate Manual High rate Charge
The Manual High rate charge is a command function and is located under the Command (‘Cmnd’) key. To prevent
accidental activation, this command can be password protected if required. Follow the instructions below.
Press ‘Next’ until the following indication is displayed:
Press ‘Enter’
With the right pointing arrow '' the digit position can be selected and with the arrow up '' an alphanumeric
character between 0 and 9 or between A and Z can be set. When all four characters are set, press ‘Enter’.
If the password is correct, the display switches to the High rate on/off selection.
Incorrect passwords will cause a jump of two positions back in the menu tree and a message ‘WRONG
PASSWORD’ is displayed.
If no password is activated the High rate selection menu will be shown directly.
The high rate charge can be switched on by pressing the “Yes” key.
To stop the high rate charge, the user can manually put the rectifier in floating charge mode via the command menu
(see the 6.6.3 paragraph) or wait for the timer times out. In this last case, the rectifier switches automatically in
floating charge mode.
The remaining high rate charge time can be read on the LCD display via the measurements menu.
See paragraph 6.5.1.
FLOATING CHARGE
Monit Confg Cmnd
SET HIGH RATE
Next Enter Exit
Start High rate?
Yes Cancel
Password: 1111
Enter
Correct password
WRONG PASSWORD
Starting from the main menu, select ‘Cmnd’.